Step 1: Mechanical Installation - Parker AC890 Product Manual

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

890SD Standalone Drive

Step 1: Mechanical Installation

Install the 890 units and associated equipment into the cubicle. The diagram shows a typical layout using
Star Point earthing for EMC compliance. Refer to Appendix C for further information.
KEY
A
Analog Clean Earth
B
Back plate
C
Cubicle
E
Dirty Earth
F
Filter (optional)
G
Star Point Earth
M
Metal Work Earth
Vent Kit with
N
(optional) Drive Brake
Unit
Fuse or
P
circuit breaker
R
AC Line Reactor
Signal/Control Screen
S
Earth
T
Auxiliary Supply
V
External Fan (Frame J)
4-2
Page
C
E
M
P
S
G
E
Figure 5.1 A Typical Cubicle Layout (wiring not shown)
N
F
D
I I T
G A L
D C D I V
R
E
DC 4Q 1 5A
1
1
O K
SE Q
R EF
E
PR O G
M
L
R
JO G
R
V
T
24V
A
890SD (Standalone) Drive: Frame G, H & J
AC
890
WARNING
b e fo re se rvi ci n g . Se e d i a g ra m. Ca p a c i t i ve sto r e d e n e rg y. Do n o t re m o v e
Ri sk o f e l e c tri c s h o ck . M o re th a n o n e l i ve ci rcu i t . Di sco n n e ct a l l s u p p l i e s
co ve r u n ti l 4 m i n u te s a f t e r su p p l y i s d i sc o n n e cte d .