Parker AC890 Product Manual page 422

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

Parameter Descriptions
FAST STOP MODE
Selects stopping mode used during a fast stop, two options ramped or coast.
Enumerated Value : Stopping Mode
FAST STOP LIMIT
Maximum time that the Drive will try to Fast Stop, before quenching.
FAST STOP TIME
Rate at which the SPEED DEMAND is ramped to zero (see REFERENCE function block)
FINAL STOP RATE
Rate at which any internally generated setpoint trims are removed. For example, the trim due to the slip compensation in
Volts/Hz control mode.
890SD Standalone Drive - Frames G, H & J
PREF: 102.05
0 : RAMPED
1 : COAST
PREF: 102.06
PREF: 102.07
PREF: 102.08
Default: 0
Default: 30.0 s
Default: 0.1 s
Default: 1200 Hz/s
Range: See below
Range: 0.0 to 3000.0 s
Range: 0.0 to 600.0 s
Range: 1 to 4800 Hz/s