Parker AC890 Product Manual page 346

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

Parameter Descriptions
ENERGY SAVING
When set TRUE, the demanded volts are reduced to minimise energy consumption if the drive is operating in a steady state at
light load.
USER FREQ 1 to 10
These parameters provide 10 frequency points, which together with the USER VOLTAGE parameters, provide the user defined
voltage profile. (USER FREQ n, USER VOLTAGE n) provide up to 10 (x,y) points on this profile. The USER FREQ
parameters are defined as a percentage of the BASE FREQUENCY parameter (refer to the MOTOR INDUCTION function
block).
USER VOLTAGE 1 to 10
These parameters provide 10 voltage points, which together with the USER FREQ parameters, provide the user defined voltage
profile. (USER FREQ n, USER VOLTAGE n) provide up to 10 (x,y) points on this profile. The USER VOLTAGE parameters
are defined as a percentage of the MOTOR VOLTAGE parameter (refer to the MOTOR INDUCTION function block).
890SD Standalone Drive - Frames G, H & J
PREF: 21.09
PREF: 21.10, 21.12, 21.14,
21.16, 21.18, 21.20, 21.22,
21.24, 21.26,21.28
PREF: 21.9, 21.11, 21.13,
21.15, 21.17, 21.19, 21.21,
21.23, 21.25,21.27, 21.29
Default: FALSE
Default: Refer to Parameter
Table
Default: Refer to Parameter
Table
Range: FALSE / TRUE
Range: 0.0 to 100.0 %
Range: 0.0 to 100.0 %
Page
D-55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

890sd

Table of Contents