Parameter Descriptions
TOTAL INERTIA
The total inertia of the motor and load. This is used as part of the speed loop Autotune feature.
STATOR RES
This parameter contains the motor model per-phase stator resistance as determined by Autotune.
LEAKAGE INDUC
This parameter contains the motor model per-phase leakage inductance as determined by Autotune.
MUTUAL INDUC
This parameter contains the motor model per-phase mutual (magnetising) inductance as determined by Autotune.
ROTOR TIME CONST
This parameter contains the motor model rotor time constant as determined by Autotune.
D-82
Page
PREF: 27.23
PREF: 27.14
PREF: 27.15
PREF: 27.16
PREF: 27.17
Default: 0.0000 kgm
2
Default: 1.5907 Ω
Default: 33.76 mH
Default: 135.02 mH
Default: 136.75 ms
Range: 0.0000 to
300.0000 kgm
2
Range: 0.0000 to 250.0000 Ω
Range: 0.00 to 300.00 mH
Range: 0.00 to 3000.00 mH
Range: 10.00 to 30000.00 ms