Wire Sizes (US/Canada)
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated (75ºC) copper
conductors assuming not more than three current-carrying conductors in raceway or cable, based on ambient temperature of
30ºC. The wire sizes allow for an ampacity of 125% of the rated input and output amperes for motor branch-circuit
conductors as specified in NEC/NFPA-70.
Catalog Number
890SD/4/0216G/..
890SD/4/0250G/..
890SD/4/0316G/..
890SD/4/0361G/..
Catalog Number
890SD/4/0216G/..
890SD/4/0250G/..
890SD/4/0316G/..
890SD/4/0361G/..
890SD (Standalone) Drive: Frame G, H & J
FRAME G : 460V 10%

CONSTANT TORQUE

Power Input
Power Output
Kcmil
250
350
600
700
QUADRATIC TORQUE
Power Input
Power Output
Kcmil
350
500
700
900
Kcmil
300
400
600
700
Kcmil
400
500
700
900
Technical Specifications
Brake Output
AWG
6
4
4
3
Brake Output
Page