X16
All digital inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool
supplied on disk. The table shows the factory defaults. The digital inputs require 24V DC which is supplied
at terminal X14/03. For further information refer to the DSE 890 Configuration Tool.
Relay outputs are volt-free, normally open contacts. Rated to 240V 3A resistive load. Alternatively they
may be used down to 1mA, 12V levels.
890SD (Standalone) Drive: Frame G, H & J
Name
Range
01
DOUT4A
open/closed
02
DOUT4B
open/closed
03
DOUT5A
open/closed
04
DOUT5B
open/closed
05
DOUT6A
open/closed
06
DOUT6B
open/closed
07
NC
08
MTR THRM A
09
MTR THRM B
890SD Standalone Drive
DIGITAL I/O
Description
Normally-open relay contacts, A & B.
Default function DOUT4 closed = healthy
Normally-open relay contacts, A & B.
Default function DOUT5 closed = running
Normally-open relay contacts, A & B.
No default function.
Not Connected - this terminal is unused
Motor thermistor connection,
or link to MTR THRM B
Motor thermistor connection,
or link to MTR THRM A