ACCESS CONTROL

SETUP::MENUS::ACCESS CONTROL
This function block contains options associated with keypad password protection, view levels, setpoint display and initial
Operator Menu selection.
Parameter Descriptions
VIEW LEVEL
Sets the level of menu to be displayed by the keypad.
Enumerated Value : View Level
PASSWORD
Setting a non-zero value enables the password feature.
CONFIG NAME
The maximum length is 16 characters. When not blank, the string is displayed as the top line of the Welcome screen.
STARTUP SCREEN
Selects which of the Operator Menu parameters will be displayed after the Welcome screen.
Enumerated Value : Startup Screen
890SD Standalone Drive - Frames G, H & J
PREF: 31.01
0 : OPERATOR
1 : BASIC
2 : ADVANCED
PREF: 31.02
PREF: 31.05
PREF: 31.06
0 : selects REMOTE SETPOINT or LOCAL SETPOINT
1 : selects parameter defined by OPERATOR MENU 1
2 : selects parameter defined by OPERATOR MENU 2
: etc.
32 : selects parameter defined by OPERATOR MENU 32
Default: 1
Default: 0000
Default:
Default: 0
Range: See below
Range: 0x0000 to 0xFFFF
Range: See below
Range: See below