Cabling Requirements for EMC Compliance

Cable Type
(for EMC Compliance)
Screen to Earth
Connection
Segregation
890xx/x/...
Length Limitations
With External AC
Supply EMC Filter
Length Limitations
With Output Choke
Length Limitations
Without Output Choke
890SD (Standalone) Drive: Frame G, H & J
Power Supply
Motor Cable
Cable
Screened/
Unscreened
armoured
Both ends
From all other
wiring (clean)
50 metres To achieve
Unlimited
EN61800-3 Table 9
restricted distribution
300 metres maximum
250 metres maximum
External AC
Supply EMC Filter
to Drive Cable
Screened/
armoured
Both ends
From all other wiring (noisy)
0.3 metres
Technical Specifications
Brake
Signal/Control
Resistor
Cable
Cable
Screened/
Screened
armoured
Both ends
Drive end only
From all other
wiring (sensitive)
25 metres
25 metres