890SD Standalone Drive
Enclosure/Environmental Information
The information here will help you to specify the enclosure to house the 890(s).
Operating Temperature
Product Enclosure Rating Cubicle Mounted only (with or without Top Vent):
Cubicle Installation
Cubicle Rating
4-6
Page
890 Operating Conditions
0°C to 40°C (32°F to 104°F), derate up to a maximum of 50°C
Derate linearly at 1% per degree centigrade for temperature
exceeding the maximum rating ambient for the drive.
IP20 - UL (c-UL) Open Type (North America/Canada) Type 1
IP00 - power terminals
The 890 must be installed to EN60204 Standard in the cubicle. For
USA, the cubicle shall meet the requirements of UL50.
Cubicle to provide the following attenuation to radiated emissions:
EMC Enclosure Standard
EN61800-3
Category C3
EN61800-3
Category C2 Restricted Distribution
EN61000-6-3
EN61800-3
Category C1 Unrestricted Distribution
EN61000-6-4
Attenuation to RF in
spectrum 30-1000MHz
NONE
10db
20db