Keypad Menus
890CD Common Bus Drive & 890SD Standalone Drive
PREF
6901 Display
27.08
*MOTOR
CONNECTION
(induction
motor
only)
71.01
PULSE ENC VOLTS The voltage output from the encoder feedback
71.02
ENCODER LINES
71.03
ENCODER INVERT When TRUE, changes the sign of the
80.01
AUTOTUNE
ENABLE
80.02
AUTOTUNE MODE Selects the Autotune operating mode.
8-25
Page
QUICK SETUP MENU
Description
This parameter contains the motor nameplate
connection.
card.
The number of lines must be set to match the
type of encoder being used. Incorrect setting
of this parameter will result in an erroneous
speed measurement.
measured speed and the direction of the
position count.
Determines whether the Autotune sequence is
operational or not. The Autotune sequence is
operational when set to TRUE and the drive is
run
Range
0= DELTA
1= STAR
10 to 20V
250 to 32767
0=FALSE
1=TRUE
0=FALSE
1=TRUE
0 : STATIONARY
1 : ROTATING
2 : SPD LOOP
ROTATING
3 : SPD LOOP
STATIONARY
890SD Standalone Drive - Frames G, H & J
Default
1
5.0
2048
0
0