Parker AC890 Product Manual page 54

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

X14
Note
The maximum permissible sum of currents from X14/03, X15/08, X15/09 is 150mA. An Alert message
will be displayed if exceeded.
890SD (Standalone) Drive: Frame G, H & J
Name
Range
01
DOUT3A
0-24V DC
02
DOUT3B
0-24V DC
03
USER 24V 0-24V DC
04
0V
0-24V DC
SUPPLY
150mA
RELAY CONTACTS
Description
Relay Output: normally-open, volt-free, 24V DC 1A
resistive load or use down to 1mA, 12V levels
(DOUT3 closed = HEALTH)
Relay Output: normally-open, volt-free, 24V DC 1A
resistive load or use down to 1mA, 12V levels
(DOUT3 closed = HEALTH)
24V DC Output, 150mA maximum load
0V reference for USER 24V output
X15/01
X14/03
(7mA each)
X15/07
X15/08
X15/09
890SD Standalone Drive
Page
4-35

Hide quick links: