Other 890 Drives on the Bus
Set the ENABLE parameter in the SLEW RATE LIMIT function block to FALSE.
This disables ramp-hold during deceleration on high link volts feature.
If in Volts/Hz motor control mode, the VOLTAGE MODE parameter in the
VOLTAGE CONTROL function block MUST be set to FIXED. This will ensure the
motor is not overfluxed by the boosted 720V DC Bus. Failure to do this may lead to
motor overheating and possible burn out.
Setting for DC VOLTS DEMAND Parameter
Drive
Voltage
Rating (V)
380V – 460V
220V – 240V
890SD (Standalone) Drive: Frame G, H & J
Under Volts
Over Volts
Trip Level (V)
Trip Level
(V)
410V
820V
205V
410V
Recommended
DC VOLTS
DEMAND
720V
370V
Operating the Drive
6-28
Page