Parker AC890 Product Manual page 443

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

SPEED FBK TRIP
SETUP::TRIPS::SPEED FBK TRIP
CLOSED-LOOP VEC Motor Control Mode only.
The speed feed back trip operates by looking at speed error and comparing it against THRESHOLD.
If the error exceeds this threshold for a period greater than DELAY, then a trip is triggered. The trip is only active while the
drive is operating in Closed-Loop Vector Control and not in Autotune. When using the drive in torque control, this trip should
be disabled to prevent nuisance tripping by setting INHIBIT to TRUE.
Torque control is defined as operating in torque or current limit, or if the TORQ DMD ISOLATE parameter in the SPEED
LOOP function block is TRUE.
Parameter Descriptions
INHIBIT
Set this parameter to TRUE to disable the speed feedback trip.
THRESHOLD
Sets a threshold below which the trip will not operate. The value of THRESHOLD is compared to the value of SPEED ERROR
(from the SPEED LOOP function block).
DELAY
Sets the time the trip must be present for before a trip is triggered.
TRIPPED
This is a diagnostic output indicating the current state of the speed feedback trip.
D-152
Page
PREF: 115.01
PREF: 115.02
PREF: 115.03
PREF: 115.04
Default: FALSE
Default: 50.00 %
Default: 10.00 %
Default: FALSE
890SD Standalone Drive - Frames G, H & J
Range: FALSE / TRUE
Range: 0.00 to 300.00 %
Range: 0.00 to 10.00 s
Range: FALSE / TRUE