EMC CAPACITORS
SETUP::MISCELLANEOUS::EMC CAPACITORS
This block allows the user to disconnect the internal EMC "Y" capacitor (DC+ to earth and DC- to earth) from the drive earth
on 890 Frames B, C & D.
Parameter Descriptions
EMC CAPACITORS
Electrically connects the internal EMC capacitors inside the product.
Enumerated Value : Internal EMC "Y " Capacitors
Isolating the capacitors in this way will lower the input bridge's immunity to surges.
Reasons for Isolation
The drive's "Y" capacitors should be electrically isolated :
when operating the drive on IT (non-earth referenced supplies)
when operating the drive in a regenerative common dc link system (remove from all drives in the system)
to prevent nuisance operation of earth leakage protection devices caused by earth leakage currents flowing in the supply
890SD Standalone Drive - Frames G, H & J
PREF: 125.01
0 : CONNECTED
1 : NOT CONNECTED
Caution
This will invalidate the EMC certification.
Default: 0
Y caps connected to earth
Y caps disconnected from earth
Range: See below
D-35
Page