Parameter Descriptions
1:MOT CUR PCNT
Sets the current level to apply (as a percentage of the permanent current of the motor) when the TYPE parameter is set to
STANDARD.
1:MOT CUR RAMP
Sets the ramp value in seconds to apply to the current setpoint when the TYPE parameter is set to STANDARD..
ELEC POS OFFSET
An electrical position offset value that compensates for deviation from the theoretical value.
For example, if the value of the ELEC POS parameter is 100° and the theoretical value is 90° (MOTOR PHASE parameter set to
U PHASE), you can apply a value of -10° to compensate for the deviation.
ELEC POS
This diagnostic displays the electrical position of the motor in degrees.
CURRENT
This diagnostic shows the current value in Amps applied to the motor.
STATE
This diagnostic displays the state of the motor.
Enumerated Value : State
D-76
Page
PREF: 156.06
PREF: 156.07
PREF: 156.16
PREF: 156.17
PREF: 156.18
PREF: 156.19
0 : NORMAL
1 : POLARIZING
Default: 50.00
Default: 1.00
Default:0.0000°
Default:
Default:
Default: 0
normal mode
the motor is under polarisation
890SD Standalone Drive - Frames G, H & J
Range: 0.00 to 100.00 %
Range: 0.10 to 20.00 s
Range: -180.0000° to
180.0000°
Range: -180.0000° to
180.0000°
Range: —.0000 A
Range: See below