FLYCATCHING
SETUP::MOTOR CONTROL::FLYCATCHING
Designed for all Motor Control Modes.
This block performs a directional speed search. It allows the Drive to seamlessly catch a spinning motor before controlling the
motor to the desired setpoint. This is especially useful for large inertia fan loads, where drafts in building air ducts can cause a
fan to `windmill'.
Parameter Descriptions
VHZ ENABLE
Enables flycatching in Volts/Hz Control mode when TRUE.
VECTOR ENABLE
Enables flycatching in Vector Control mode when TRUE.
START MODE
The mode of operation for the flycatching sequence software.
Enumerated Value : Start Mode
SEARCH MODE
The type of speed search carried out by the flycatching sequence.
Enumerated Value : Search Mode
D-58
Page
PREF: 69.01
PREF: 69.15
PREF: 69.02
0 : ALWAYS
1 : TRIP OR POWERUP
2 : TRIP
PREF: 69.03
0 : BIDIRECTIONAL
1 : UNIDIRECTIONAL
Default: FALSE
Default: FALSE
Default: 0
Default: 0
Range: FALSE / TRUE
Range: FALSE / TRUE
Range: See below
Range: See below