Trips and Fault Finding
6511
6901
Keypad
Keypad
Display
Display
I HI
CURRENT LIMIT
A24SC
24V FAILURE
LSPD
LOW SPEED OVER I
PHAS
PHASE FAIL
ENC 1
FBK ENCODER FAIL
SHRT
DESAT (OVER I)
9-8
Page
Description
V/Hz mode only: If the
current exceeds 180% of
induction stack rated
current for a period of 1
second, the drive will trip.
This is caused by shock
loads
The 24V customer output
has fallen below 17V
The motor is drawing too
much current (>100%) at
zero output frequency
Possible Reason for Trip
 Remove the cause of the shock load
 24V customer output is short circuited
 Excessive loading
 FIXED BOOST and/or AUTO BOOST set too high
(refer to FLUXING menu at level 3)
 One or more input phases not present
 Encoder fault
 Instantaneous overcurrent. Refer to
OVERCURRENT in this table