Technical Specifications
AC Line Choke
Frame G, H, J drives MUST use an AC Line Choke. However, where a drive is individually supplied from a dedicated
transformer with the required impedance, the AC Line Choke is not required.
Where a system comprises a number of Frame G, H and J drives connected to a common supply, a separate AC Line Choke is
required in the supply to each drive.
When an EMC external ac supply filter is used, the AC Line Choke must be fitted between the filter and the drive.
Failure to provide the correct line impedance will severely reduce the drives lifetime and could result in catastrophic
The required AC Line Choke line impedance is nominally 3% of the drive rating.
Parker Hannifin Manufacturing can supply the following ac line chokes:
Frame
Constant/Quadratic
Size
Torque Rating
kW @ 380V Hp @ 460V
H
200/250
220/250
250/300
280/315
J
315/355
E-24
Page
failure of the drive.
Inductance/Phase Maximum Continuous
(H)
50
300/400
350/400
35
400/450
450/500
500/550
Caution
AC Line Current-
Quadratic Torque
(A rms)
474
461
474
461
574
529
601
581
676
636
Peak Current @
Parker
150% Constant
Part No.
Torque Rating
(A peak)
915
CO389936U402
915
995
995
1180
CO389936U403
1180
1295
1295
1430
1430