Electrical Ratings (Induction): 890SD Frame G, 400V
Power Supply = 380-460V ±10%, 50/60Hz 5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Suitable for earth referenced (TN) and non-earth referenced (IT) supplies.
Model Number
(Europe)
FRAME G :
Prospective short circuit current 100kA maximum.
Quadratic Torque
Output Overload Motoring 110% for 60s (V/Hz mode)
890SD-433216G..
890SD-433250G..
890SD-433316G..
890SD-433361G..
890SD (Standalone) Drive: Frame G, H & J
Catalog Number
Motor
Power
(North America)
132kW
890SD/4/0216G/..
200hp
150kW
890SD/4/0250G/..
250hp
180kW
890SD/4/0316G/..
300hp
220kW
890SD/4/0361G/..
350hp
Output
AC
Heatsink
Current
Input
Power
(A)
Current
Loss (W)
(A)
(notes
1 & 2)
260
247
2590
260
239
302
297
3169
302
288
361
341
3635
361
358
420
402
4032
420
411
Technical Specifications
Total
Maximum
Input
Bridge I
Power
Switching
Loss
Frequency
(A
(W)
(kHz)
(note 9)
2920
2.5
304000
2.5
304000
3482
2.5
304000
2.5
304000
3967
2.5
813000
2.5
813000
4409
2.5
813000
2.5
813000
t