890CD Common Bus Drive & 890SD Standalone Drive
PREF
6901 Display
70.01
QUADRATIC
TORQUE
70.13
MOTOR CURRENT This parameter contains the motor nameplate
890SD Standalone Drive - Frames G, H & J
QUICK SETUP MENU
Description
% OF RATED MOTOR CURRENT
100% overload for 30s (Heavy Duty)
150%
127.5%
105%
100%
30
60
FALSE - CONSTANT: Inverse time allows
150% overload for 60s, then ramps back the
current limit to 105% over a 10s period. At a
lower load, the overload area remains the
same, e.g. at 127.5% load for 120s - after
120s has expired, the output of the inverse
time function is ramped back over a 10s
period from 150% as before.
TRUE - QUADRATIC: current limit is set to
110% motor current, inverse time delay is set
to 30s
full-load line current
Range
0=FALSE
1=TRUE
TIME (s)
Note that 890 Frames
B, C & D have no
quadratic torque current
rating.
0.01 to 999.99A
Keypad Menus
Default
0