Parker AC890 Product Manual page 55

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

890SD Standalone Drive
X15
All digital inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool
supplied on disk. The table shows the factory defaults. The digital inputs require 24V DC which is supplied
at terminal X14/03. For further information refer to the DSE 890 Configuration Tool.
Note
The maximum permissible sum of currents from X14/03, X15/08, X15/09 is 150mA. The load on X15/08
& X15/09 connects from these pins to X14/04 (0V). An Alert message will be displayed if exceeded.
4-36
Page
Name
Range
01
DIN1
0-24V DC
02
DIN2
0-24V DC
03
DIN3
0-24V DC
04
DIN4
0-24V DC
05
DIN5
0-24V DC
06
DIN6
0-24V DC
07
DIN7
0-24V DC
08
DIN8/DOUT1
0-24V DC
09
DIN9/DOUT2
0-24V DC
SUPPLY
150mA
DIGITAL I/O
Description
Digital Input 1 (default = JOG)
Digital Input 2 - (default = RUN)
Digital Input 3 - (default = STOP)
Digital Input 4 - (default = REVERSE)
Digital Input 5 - (default = unassigned). Refer to I/O
TRIPS::EXT TRIP MODE for special function
Digital Input 6 - (default = unassigned)
Digital Input 7 - (default = unassigned)
Digital Input/output 1 -
(default = digital output: RUNNING)
Digital Input/output 2 -
(default = digital output: ZERO SPEED)
X15/01
X14/03
(7mA each)
X15/07
X15/08
X15/09
890SD (Standalone) Drive: Frame G, H & J