890CD Common Bus Drive & 890SD Standalone Drive
PREF
6901 Display
27.06
MAG CURRENT
(induction
motor
only)
27.14
STATOR RES
(induction
motor
only)
27.15
LEAKAGE INDUC
(induction
motor
only)
27.16
MUTUAL INDUC
(induction
motor
only)
27.17
ROTOR TIME
CONST
(induction
motor
only)
890SD Standalone Drive - Frames G, H & J
QUICK SETUP MENU
Description
This parameter contains the motor model no-
load line current as determined by the
Autotune, or taken from the motor nameplate
This parameter contains the motor model per-
phase stator resistance as determined by
Autotune.
This parameter contains the motor model per-
phase leakage inductance as determined by
Autotune.
This parameter contains the motor model per-
phase mutual inductance as determined by
Autotune.
This parameter contains the motor model
rotor time constant as determined by
Autotune.
Keypad Menus
Range
0.00 to 3276.70 A
0.0000 to 250.0000
0.00 to 300.00mH
0.00 to 3000.00mH
10.00 to 3000.00ms
Default
product
code
dependent
product
code
dependent
product
code
dependent
product
code
dependent
product
code
dependent
8-26