Parker AC890 Product Manual page 304

Frame g, h & j
Hide thumbs Also See for AC890:
Table of Contents

Advertisement

Parameter Descriptions
INITIAL DELAY 2
Determines the delay for the first restart attempt when the trip is included in TRIGGER 2.
The delay is measured from all error conditions clearing.
ATTEMPT DELAY 2
Determines the delay between restart attempts for a trip included in TRIGGER 2. The delay is measured from all error
conditions clearing.
TRIGGER 2 WORD 1 to
TRIGGER 2 WORD 6
Allows Auto Restart to be enabled for a selection of trip conditions.
If a trip is included in both TRIGGER 1 WORD 1 and TRIGGERS WORD 1 for instance, then the times associated with
TRIGGER 1 WORD 1 will take priority.
Refer to page D-180: "Hexadecimal Representation of Trips" for an explanation of the four-digit codes.
PENDING
Indicates that an auto restart will occur after the programmed delay.
RESTARTING
Indicates that an auto restart is occurring. TRUE for a single block diagram execution cycle.
ATTEMPTS LEFT
Indicates the number of attempts left before an external fault reset is required.
TIME LEFT
When in the Restarting state, this parameter indicates the time left before an auto restart attempt will be permitted. When non-
zero, this value is unaffected by changes to ATTEMPT DELAY 1.
890SD Standalone Drive - Frames G, H & J
PREF: 93.07
PREF: 93.08
PREF: 93.09, 93.10, 93.17,
93.18, 93.21, 93.22
PREF: 93.11
PREF: 93.12
PREF: 93.13
PREF: 93.14
Default: —.x s
Default: —.x s
Default: 0000
Default: FALSE
Default: FALSE
Default: 5
Default: —.x s
Range: 0.0 to 600.0 s
Range: 0.0 to 600.0 s
Range:0x0000 to 0xFFFF
Range: FALSE / TRUE
Range: FALSE / TRUE
Range: —.
Range: —.x s
Page
D-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

890sd

Table of Contents