Parameter Descriptions
DECEL TIME
Determines the time in which the speed setpoint is ramped to zero. This is expressed as the time to ramp from MAX SPEED to
zero.
INITIAL STEP
This parameter sets the initial speed reduction step at the start of the power loss control sequence.
TIME LIMIT
Determines the maximum allowed time of the Power Loss Ride-Through sequence. Once timeout is reached, the drive is
allowed to Coast to Stop and eventually trip on UNDERVOLTS.
PWR LOSS ACTIVE
This diagnostic is set to TRUE while the Power Loss Ride-Through sequence is active.
890SD Standalone Drive - Frames G, H & J
PREF: 112.05
PREF: 112.08
PREF: 112.06
PREF: 112.07
Default: 5.00 s
Default: 0.00 %
Default: 30.00 s
Default: FALSE
Range: 0.01 to 300.00 s
Range: 0.00 to 100.00 %
Range: 0.00 to 300.00 s
Range: FALSE / TRUE
D-115
Page