Figure 310: M7I Router Cooling System And Airflow; Figure 311: M10I Router Cooling System Components And Airflow - Juniper M Series Monitoring And Troubleshooting Manual

Hide thumbs Also See for M Series:
Table of Contents

Advertisement

Figure 310: M7i Router Cooling System and Airflow

Related
Documentation
M10i Router Redundant Cooling System Components

Figure 311: M10i Router Cooling System Components and Airflow

Copyright © 2012, Juniper Networks, Inc.
Checklist for Monitoring Redundant Cooling System Components on page 623
The M10i router cooling system consists of two fan trays, located along the left and right
side of the chassis, that provide side-to-side cooling (see
connect directly to the router midplane. Each fan tray is a single unit containing eight
individually fault-tolerant fans. If a single fan fails, the remaining fans continue to function
indefinitely. For proper airflow, the primary fan tray should be installed in slot
slot looking at the chassis from the rear) and must be installed for proper cooling at all
times. The redundant fan tray, if present, should be installed in slot
fan tray provides additional cooling and redundancy. The fan tray is hot-removable and
hot-insertable.
CAUTION:
Do not remove both fan trays for more than one minute while the
router is operating. The fans are the sole source of cooling, and the router
will overheat when they are absent.
Chapter 31: Monitoring Redundant Cooling System Components
Figure 311 on page
627). They
(the left
1
0
on the right. This
627

Advertisement

Table of Contents
loading

This manual is also suitable for:

T series

Table of Contents