8.9 Limiting Torque

The SERVOPACK provides the following four methods for limiting output torque to protect the machine.
Setting
Level
1
Internal torque limit
2
External torque limit
3
Torque limiting by analog voltage reference
4
External torque limit + Torque limiting by analog voltage reference

8.9.1 Internal Torque Limit (Limiting Maximum Output Torque)

Maximum torque is always limited to the values set in the following parameters.
Pn402
Forward Torque Limit
Pn403
Reverse Torque Limit
The settings in these parameters are constantly enabled. The setting unit is a percentage of rated torque.
If the torque limit is set higher than the maximum torque of the servomotor, the maximum torque of the servomotor is used
(as is the case with the 800% factory setting).
Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.
Limiting Method
Setting Range
Setting Unit
0 to 800
%
Setting Range
Setting Unit
0 to 800
%
No Internal Torque Limit
(Maximum Torque Can Be Output)
Speed
Maximum torque
Speed
Factory Setting
800
Speed
Factory Setting
800
Internal Torque Limit
Pn403
t
Pn402
Speed
Limiting torque
8-69
8.9 Limiting Torque
Reference Section
8.9.1
8.9.2
8.9.3
8.9.4
Position
Torque
Setting Validation
Immediately
Position
Torque
Setting Validation
Immediately