9 Adjustments
9.4.5 Using the Mode Switch (P/PI Switching)
With this setting, the speed loop is switched to P control when the
value of torque reference input exceeds the torque set in parameter
Pn10C. The factory default setting for the torque reference detection
point is 200% of the rated torque (Pn10C = 200).
Operating Example
If the mode switch function is not being used and the SERVOPACK is always operated with PI control, the speed of the
motor may overshoot or undershoot due to torque saturation during acceleration or deceleration. The mode switch function
suppresses torque saturation and eliminates the overshooting or undershooting of the motor speed.
With this setting, the speed loop is switched to P control when the value
of speed reference input exceeds the speed set in parameter Pn10D.
Operating Example
In this example, the mode switch is used to reduce the settling time. It is necessary to increase the speed loop gain to reduce
the settling time. Using the mode switch suppresses overshooting and undershooting when speed loop gain is increased.
Increase speed loop gain.
Using the Torque Reference Level to Switch Modes (Factory Setting)
Without Mode Switching
Overshoot
Motor
speed
Undershoot
Time
Using the Speed Reference Level to Switch Modes
Without Mode Switching
Speed
reference
Motor
speed
Long settling time
Overshoot
Motor
speed
Undershoot
Time
Motor
speed
Motor speed
Motor
speed
9-20
Reference speed
Speed
Torque reference
+Pn10C
Torque
reference 0
-Pn10C
PI control
PI
P
With Mode Switching
Time
Speed reference
Speed
Pn10D
P control
PI
With Mode Switching
Settling time
Motor speed
P
PI control
Motor
speed
Time
PI control