Delta CT2000 Series User Manual page 64

Table of Contents

Advertisement

The following table refers to IEC 60034-17 shows specification of the length of shielding
cable for CT2000 series motor. It applies to the motors which rated voltage is under 500Vac,
peak-peak voltage isolation rating is above (including) 1.35kV:
Model
HP
VFD110CT43F00B
15
VFD110CT43A21C
VFD150CT43F00B
20
VFD150CT43A21C
VFD185CT43F00B
25
VFD185CT43A21C
VFD220CT43F00B
30
VFD220CT43A21C
VFD300CT43F00B
40
VFD300CT43A21C
VFD370CT43F00B
50
VFD370CT43A21C
VFD450CT43F00B
60
VFD450CT43A00C
VFD550CT43F00B
75
VFD550CT43A00C
VFD750CT43F00A6
100
VFD900CT43F00A8
125
Rated Amps
Without output AC reactor
(Arms)
Shielding
Light
Heavy
cable
duty
duty
(meter)
22.5
17
30
23
36
30
45
36
56
43
72
57
91
69
110
86
144
105
180
143
7-11
Chapter 7 Optional AccessoriesCT2000 Series
Un-shieldin
g cable
(meter)
100
150
100
150
100
150
100
150
100
150
100
150
150
225
150
225
150
225
150
225
Output AC reactor
Shielding
Un-shielding
cable (meter)
cable (meter)
150
225
150
225
150
225
150
225
150
225
150
225
225
325
225
325
225
325
225
325

Hide quick links: