Delta CT2000 Series User Manual page 289

Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCT2000 Series
High-voltage
at DC si de
Ov er-v ol tage
detec ti on
level
Output
frequency
Selection for Over-voltage Stall Prevention
Settings
 When Pr.06-02 is set to 1, the drive will maintain DCbus voltage when decelerating and prevent
OV.
Over-current Stall Prevention during Acceleration
Settings
 If the motor load is too large or drive acceleration time is too short, the AC drive output current may
increase abruptly during acceleration and it may cause motor damage or trigger protection
functions (OL or OC). This parameter is used to prevent this situation.
previous deceleration time
requir ed time for decelerating to 0Hz when over- voltage
stall prevention is enabled.
0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
60Hz
370Vdc
0
230V Series
Light duty: 0~160% (100%: drive's rated current)
Heavy duty: 0~180% (100%: drive's rated current)
12.1-06-2
Deceleration c har acteristic
when Ov er-Voltage Stall
Pr ev ention enabled
Output Frequency
DCBUS Voltage
310Vdc
Time
F requenc y Held
Time
Factory Setting: 0
Time
Factory Setting: 120
Factory Setting: 150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents