Filter Time for PID Feedback
Settings
 When the PID control function is normal, it should calculate within a period of time and close to the
setpoint value.
 Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr.08-13 PID Deviation Level and exceeds Pr.08-14
setting, the PID control fault occurs. The treatment will be done as Pr.08-09 setting.
PID Compensation Selection
Settings
PID Compensation
Settings
Setting of Sleep Mode Function
Settings
Wake-up Integral Limit
Settings
Enable PID to Change the Operation Direction
Settings
Wakeup Delay Time
Settings
PID Control Flag
Settings
Chapter 12 Description of Parameter SettingsCT2000 Series
0.1~300.0 sec
0: Parameter setting
1: Analog input
-100.0~+100.0%
0: Follow PID output command
1: Follow PID feedback signal
0.0~200.0%
0: Disable change of direction
1: Enable change of direction
0.00~600.00 sec.
Bit 0 = 1, PID reverse running must follow the setting of Pr00-23.
Bit 0 = 0, PID reverse running follow PID's calculated value.
12.1-08-7
Factory Setting: 5.0
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
Factory Setting: 50.0
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0