The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified output terminal will be activated (Pr.02-13~02-14, Pr.02-36,
02-37 is set to 18). Pr.02-19 can't be set to 0.
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555, it
means that real counter value is between 55,550 to 55,559.
Preliminary Counting Value Attained (not return to 0)
Settings
When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.
Di spl ay va lu e
[00 -04 =0 1]
[02-06=23]
TRG
Counter Trigger
( ou tpu t sig na l)
P re li min ar y Cou nte r V al ue
RY 1 P r.0 2- 13 =17
Te rmi na l Co un ter Va lu e
RY 2 P r.0 2- 14 =18
Digital Output Gain(DFM)
Settings
It is used to set the signal for the digital output terminals (DFM-DCM) and digital frequency output
(pulse X work period=50%). Output pulse per second = output frequency X Pr.02-21.
Desired Frequency Attained 1
Settings
The Width of the Desired Frequency Attained 1
Settings
Desired Frequency Attained 2
Settings
The Width of the Desired Frequency Attained 2
Settings
Once output frequency reaches desired frequency and the corresponding multi-function output
terminal is set to 3 or 4 (Pr.02-13, 02-14, 02-36, and 02-37), this multi-function output terminal will
be ON.
Chapter 12 Description of Parameter SettingsCT2000 Series
0~65535
02 -13, 02- 14, 0 2-3 6, 02 -37
02 -14=1 7
1~166
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
12.1-02-17
02 -20=3
02 -19=5
Factory Setting: 0
1.0msec
1.0msec
Th e wi dth of tr ig ge r si gn al
Factory Setting: 1
Factory Setting: 60.00/50.00
Factory Setting: 2.00
Factory Setting: 60.00/50.00
Factory Setting: 2.00