Chapter 12 Description of Parameter SettingsCT2000 Series
When malfunction occurs, user can check the status of multi-function input/output terminals. If it
happens again, it will overwrite the previous record.
When malfunction occurs, please check the drive status (communication address 2119H). If
malfunction happens again, the previous record will be overwritten by this parameter.
Pr.06-45 defines how the drive will operates when output phase loss occur.
PLC1.ir
Status of Multi-function Input Terminal at Malfunction
Settings
0000h~FFFFh
Status of Multi-function Output Terminal at Malfunction
Settings
0000h~FFFFh
Drive Status at Malfunction
Settings
0000H~FFFFh
Reserved
Reserved
Treatment to Output Phase Loss Detection (OPHL)
Settings
0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
Deceleration Time of Output Phase Loss
Settings
0.000~65.535 sec
Current Bandwidth
Settings
0.00~100.00%
DC Brake Time of Output Phase Loss
Settings
0.000~65.535 sec
LvX Auto Reset
Settings
0: Disable
1: Enable
Time for Input Phase Loss Detection
Settings
0.00~600.00 sec
12.1-06-14
Factory Setting: Read only
Factory Setting: Read only
Factory Setting: Read only
Factory Setting: 3
Factory Setting:0.500
Factory Setting:1.00
Factory Setting:0.000
Factory Setting: 0
Factory Setting:0.20