User Defined Value
Settings
 Pr.00-27 will show user defined value when Pr.00-26 is not set to 0.
 User defined function is valid when Pr.00-20 is set to digital keypad control or RS-285
communication input control.
Reserved
LOCAL/REMOTE Selection
Settings
 The factory setting of Pr.00-29 is 0 (standard Hand-Off-Auto function). The AUTO frequency and
source of operation can be set by Pr.00-20 and Pr.00-21, and the HAND frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. AUTO/HAND mode can be selected or switched by
using digital keypad(KPC-CC01) or setting multi-function input terminal MI= 41, 42.
 When external terminal MI is set to 41 and 42 (AUTO/HAND mode), the settings Pr.00-29=1,2,3,4
will be disabled. The external terminal has the highest priority among all command, Pr.00-29 will
always function as Pr.00-29=0, standard HOA mode.
 When Pr.00-29 is not set to 0, Local/Remote function is enabled, the top right corner of digital
keypad (KPC-CC01) will display "LOC" or "REM" (the display is available when KPC-CC01 is
installed with firmware version higher than version 1.021). The LOCAL frequency and source of
operation can be set by Pr.00-20 and Pr.00-21, and the REMOTE frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. Local/Remote function can be selected or switched
by using digital keypad(KPC-CC01) or setting external terminal MI=56. The AUTO key of the digital
keypad now controls for the REMOTE function and HAND key now controls for the LOCAL
function.
 When MI is set to 56 for LOC/REM selection, if Pr.00-29 is set to 0, then the external terminal is
disabled.
 When MI is set to 56 for LOC/REM selection, if Pr.00-29 is not set to 0, the external terminal has
the highest priority of command and the ATUO/HAND keys will be disabled.
Source of the Master Frequency Command(HAND)
Settings
Chapter 12 Description of Parameter SettingsCT2000 Series
Read only
0: Standard HOA function
1: Switching Local/Remote, the drive stops
2: Switching Local/Remote, the drive runs as the REMOTE setting for
frequency and operation status
3: Switching Local/Remote, the drive runs as the LOCAL setting for frequency
and operation status
4: Switching Local/Remote, the drive runs as LOCAL setting when switch to
Local and runs as REMOTE setting when switch to Remote for frequency
and operation status.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
12.1-00-15
Factory Setting: Read only
Factory Setting: 0
Factory Setting: 0