Freq uen cy
Output
Frequenc y
Moto r
Ro tatio n
Spe ed
Oper atio n
Co mmand
 Ramp to stop: the AC motor drive decelerates from the setting of deceleration time to 0 or
minimum output frequency (Pr. 01-09) and then stop (by Pr.01-07).
 Coast to stop: the AC motor drive stops the output instantly upon a STOP command and the
motor free runs until it comes to a complete standstill.
(1) It is recommended to use "ramp to stop" for safety of personnel or to prevent material from
being wasted in applications where the motor has to stop after the drive is stopped. The
deceleration time has to be set accordingly.
(2) If the motor free running is allowed or the load inertia is large, it is recommended to select
"coast to stop". For example, blowers, punching machines and pumps
 The stop method of the torque control is also set by Pr.00-22.
Control of Motor Direction
Settings
 This parameter enables the AC motor drives to run in the forward/reverse Direction. It may be used
to prevent a motor from running in a direction that would consequently injure the user or damage
the equipment.
Memory of Frequency Command
Settings
 If keypad is the source of frequency command, when Lv or Fault occurs the present frequency
command will be saved in this parameter.
User Defined Characteristics
Settings
Chapter 12 Description of Parameter SettingsCT2000 Series
Stops acc ording t o
dec eler ation time
RUN
STOP
Ramp to Stop and Coast to Stop
0: Enable forward/ reverse
1: Disable reverse
2: Disable forward
Read only
Bit 0~3: user define on decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
12.1-00-13
Freq uen cy
Output
Frequenc y
Moto r
Ro tatio n
Spe ed
Time
Oper atio n
RUN
Co mmand
Factory Setting:
Fr ee r unning
to stop
Time
STOP
Factory Setting: 0
Read Only
Factory Setting: 0