Chapter 12 Description of Parameter SettingsCT2000 Series
 Pr.02-09 set to 1: it will increase/decrease frequency command (F) by the setting of
acceleration/deceleration (Pr.01-12~01-19) and only be valid during operation.
Mu lti -fu ncti on
i np ut te rmi na l
1 0 Fr eq ue ncy
i ncr ea sed comma nd
Digital Input Response Time
Settings
 This parameter is used to set the response time of digital input terminals FWD, REV and MI1~MI8.
 It is used for digital input terminal signal delay and confirmation. The delay time is confirmation
time to prevent some uncertain interference that would cause error in the input of the digital
terminals. Under this condition, confirmation for this parameter would improve effectively, but the
response time will be somewhat delayed.
Digital Input Operation Direction
Settings 0000h~FFFFh(0:N.O. ; 1:N.C.)
 The setting of this parameter is In hexadecimal.
 This parameter is used to set the input signal level and it won't be affected by the SINK/SOURCE
status.
 Bit0 is for FWD terminal, bit1 is for REV terminal and bit2 to bit15 is for MI1 to MI14.
 User can change terminal status by communicating.
For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed
command 2). Then the forward + 2
to set Pr.02-12=9 by communication and it can forward with 2
any multi-function terminal.
Bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MI14 MI13 MI12 MI11 MI10 MI9 MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1
Multi-function Output 1 (Relay1)
Multi-function Output 2 (Relay2)
Multi-function Output 3 (MO1)
Multi-function Output 4 (MO2)
Output terminal of I/O extension card (MO10)
Fr eq ue ncy
Fr eq ue ncy
co mman d
0.000~30.000 sec
nd
step speed command=1001(binary)=9 (Decimal). Only need
12.1-02-10
In cre ase d b y acce le ra tio n ti me
OFF
ON
nd
step speed. It doesn't need to wire
Ti me
Factory Setting: 0.005
Factory Setting: 0000
Factory Setting: 11
Factory Setting: 1
Factory Setting: 66