the accuracy of angles detected will be affected. Therefore, refer to the setting of Pr01-01
before adjusting this parameter.
If the setting value of Pr00-17 is lower Pr10-51*10, then increase the frequency of carrier
wave.
Injection Magnitude
Settings
The parameter is magnitude command of high frequency injection signal when IPM HFI
sensorless control mode.
Increase the parameter can get the more accurate estimated value of angle. But the noise of
electromagnetic might be louder if the setting value is too high.
To get the parameter when motor's parameter is "Auto". And the parameter will influence the
accuracy of angel's estimation.
When the ratio of salient pole (Lq/Ld) is lower, increase Pr10-52 to make angle detection be
accurate.
PM Motor Initial Rotor Position Detection Method
Settings
It is suggested to set as "2" if it's IPM; set as "3" if it's SPM. If there is bad effect when set as
"2" or "3", then set as "1".
11. Parameters for speed adjustment
Torque Compensation Gain (V/F and SVC control mode)
Settings
The parameter influences the output current during the running process. There will be less
effect on the low speed area.
Increase the setting value if the current with no-load is too high. But it might also cause the
motor to vibrate. If the motor vibrates during the operation, decrease the setting value.
Chapter 12 Description of Parameter SettingsCT2000 Series
0.0~200.0V
0: No function
1: DC injection
2: High frequency injection
3: Pulse injection
4~5: Reserved
0~10
12.2-00-6
Factory Setting: 15/30V
Factory Setting: 0
Factory Setting: 0