02 Digital Input/Output Parameter
2-wire/3-wire Operation Control
Settings
 It is used to set the operation control method:
Pr.02-00
2-wire mode 1
FWD/STOP
REV/STOP
2-wire mode 2
RUN/STOP
REV/FWD
3-wire operation control
Multi-function Input Command 1 (MI1)
(MI1= STOP command when in 3-wire operation control)
Multi-function Input Command 2 (MI2)
Multi-function Input Command 3 (MI3)
Multi-function Input Command 4 (MI4)
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Input terminal of I/O extension card (MI10)
Input terminal of I/O extension card (MI11)
0: 2 wire mode 1
1: 2 wire mode 2
2: 3 wire mode
0
1
3
Chapter 12 Description of Parameter SettingsCT2000 Series
 This parameter can be set during operation.
Control Circuits of the External Terminal
FWD/S TOP
RE V/S TOP
RUN/S TOP
FW D/RE V
RUN
STO P
RE V/FWD
12.1-02-1
Factory Setting: 0
FWD:( "O PE N":S TOP )
( "CLO S E":FWD)
REV :("O PE N": STO P)
("CL OS E ": REV )
DCM
VFD-C T
F WD:("O P EN":S TOP )
( "CLO S E":RUN )
RE V:( "O P EN": FW D)
("CL OS E ": REV )
D CM
VFD-CT
FWD "CL OS E":RUN
MI1 "O PE N":STOP
R EV /FWD "O PE N": FWD
"CLO SE ": RE V
DCM
VFD- CT
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4