Chapter 12 Description of Parameter SettingsCT2000 Series
Terminal MI15 MI14 MI13 MI12 MI11 MI10 MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1 REV FWD
Status
0
MI10~MI15 are the terminals for extension cards (Pr.02-26~02-31).
If REV, MI1 and MI6 are ON, the value is 0000 0000 1000 0110 in binary and 0086h in HEX. When
Pr.00-04 is set to "16" or "19", it will display "0086h" with LED U is ON on the keypad KPC-CE01. The
setting 16 is the status of digital input by Pr.02-12 setting and the setting 19 is the corresponding CPU
pin status of digital input, the FWD/REV action and the three-wire MI are not controlled by Pr.02-12.
User can set to 16 to monitor digital input status and then set to 19 to check if the wire is normal.
4. Assume that RY1: Pr.02-13 is set to 9 (Drive ready). After applying the power to the AC motor drive, if
there is no other abnormal status, the contact will be ON. The display status will be shown as follows.
N.O. switch status:
Terminal
Reserved
Status
0
0
At the meanwhile, if Pr.00-04 is set to 17 or 20, it will display in hexadecimal "0001h" with LED U is ON
on the keypad. The setting 17 is the status of digital output by Pr.02-18 setting and the setting 20 is the
corresponding CPU pin status of digital output. User can set 17 to monitor the digital output status and
then set to 20 to check if the wire is normal.
5. Setting 8: 100% means the motor rated torque. Motor rated torque = (motor rated power x60/2π)/motor
rated speed
6. If Pr.00-04 = 25, when display value reaches 100.00%, the drive will show "oL" as an overload warning.
7. If Pr.00-04 = 38,
Bit 0: The drive is running forward.
Bit 1: The drive is running backward.
Bit 2: The drive is ready.
Bit 3: Errors occurred on the drive.
Bit 4: The drive is running.
Bit 5: Warnings on the drive.
Coefficient Gain in Actual Output Frequency
Settings 0.00~160.00
 This parameter is to set coefficient gain in actual output frequency. Set Pr.00-04= 31 to display the
calculation result on the screen (calculation = output frequency * Pr.00-05).
Software Version
Settings Read only
Parameter Protection Password Input
Settings 0~65535
Display
 This parameter allows user to enter their password (which is set in Pr.00-08) to unlock the
parameter protection and to make changes to the parameter.
 Pr.00-07 and Pr.00-08 are used to prevent the personal misoperation.
 When the user have forgotten the password, clear the setting by input 9999 and press ENTER key,
then input 9999 again and press Enter within 10 seconds. After decoding, all the settings will
return to factory setting.
0
0
0
0
Reserved
0
0
0
0
0
0~4 (the times of password attempts)
0
0
0
1
0
Reserved
0
0
0
0
0
12.1-00-4
1
1
0
0
0
MO2 MO1 Reserved RY2 RY1
0
0
0
Factory Setting: 1.00
Factory Setting: #.#
Factory Setting: 0
0
0
1