Delta CT2000 Series User Manual page 205

Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCT2000 Series
Source of the Master Frequency Command(AUTO)
Settings
 It is used to set the source of the master frequency in AUTO mode.
 Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
 The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal used
to switch AUTO/HAND mode. The highest priority is the mutli-function input terminal. When the
external terminal is OFF, the drive won't receive any operation signal and can't execute JOG.
Source of the Operation Command (AUTO)
Settings
 It is used to set the source of the operation frequency in AUTO mode.
 When the operation command is controlled by the keypad KPC-CC01, keys RUN, STOP and JOG
(F1) are valid.
Stop Method
Settings
 The parameter determines how the motor is stopped when the AC motor drive receives a valid stop
command.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16 without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen card
4: Reserved
5: Communication card (not includes CANopen card)
0: Ramp to stop
1:Coast to stop
12.1-00-12
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents