Chapter 11 Summary of Parameter SettingsCT2000 Series
06 Protection Parameters
Pr.
Explanation
06-00
Low Voltage Level
06-01
Over-voltage Stall Prevention
Selection for Over-voltage Stall
 06-02
Prevention
Over-current Stall Prevention
06-03
during Acceleration
Over-current Stall Prevention
06-04
during Operation
Accel. /Decel. Time Selection of
06-05
Stall Prevention at Constant
Speed
Over-torque Detection Selection
06-06
(OT1)
Over-torque Detection Level
06-07
(OT1)
Over-torque Detection Time
06-08
(OT1)
Over-torque Detection Selection
06-09
(OT2)
Over-torque Detection Level
06-10
(OT2)
Over-torque Detection Time
06-11
(OT2)
 06-12
Current Limit
Electronic Thermal Relay
06-13
Selection (Motor 1)
Electronic Thermal Characteristic
06-14
for Motor 1
Heat Sink Over-heat (OH)
06-15
Warning
06-16
Stall Prevention Limit Level
06-17
Present Fault Record
Settings
460V:
Frame A to D: 300.0~440.0Vdc
Frame E and frames above E: 380.0~440.0V
0: Disabled
460V: 0.0~900.0Vdc
0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
Light duty: 0~160%(100%: drive's rated current)
Heavy duty: 0~180%(100%: drive's rated current)
Light duty: 0~160%(100%: drive's rated current)
Heavy duty: 0~180%(100%: drive's rated current)
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operate after detection
4: Over-torque detection during operation, stop
operation after detection
10~250% (100%: drive's rated current)
0.0~60.0 sec.
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop
operation after detection
10~250% (100%: drive's rated current)
0.0~60.0 sec.
0~250% (100%: drive's rated current)
0: Inverter motor
(fan doesn't run with the axel synchronously )
1: Standard motor
(fan runs with the axel synchronously)
2: Electronic thermal relay disabled
30.0~600.0 sec.
0.0~110.0℃
0~100% (Pr.06-03, Pr.06-04)
0: No fault record
11-22
Factory
Setting
360.0
400.0
760.0
0
120
150
120
150
0
0
120
0.1
0
120
0.1
150
2
60.0
85.0
50
0