Chapter 8 Optional Cards CT2000 Series
Parameter
IP setting
P09-75
IP address -1
P09-76
IP address -2
P09-77
IP address -3
P09-78
IP address -4
P09-79
Netmask -1
P09-80
Netmask -2
P09-81
Netmask -3
P09-82
Netmask -4
P09-83
Default gateway -1
P09-84
Default gateway -2
P09-85
Default gateway -3
P09-86
Default gateway -4
P09-87
Disconnecting CMC- MOD01 from VFD-C2000
1.
Switch off the power supply of VFD-C2000.
2.
Remove the two screws (shown in Figure 6).
3.
Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off
the card clip (shown in Figure 7).
4.
Twist opens the other card clip to remove the PCB (shown in Figure 8).
Basic Registers
BR#
R/W
Model name
#0
R
Firmware
#1
R
version
Release date of
#2
R
the version
#11
R/W
Modbus Timeout Pre-defined setting: 500 (ms)
#13
R/W
Keep Alive Time Pre-defined setting: 30 (s)
Function
Set value (Dec)
[Figure 6]
[Figure 8]
Content
Set up by the system; read only. The model code of
CMC-MOD01=H'0203
Displaying the current firmware version in hex, e.g. H'0100 indicates the
firmware version V1.00.
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for
"month"; 100s digit and 10s digit are for "day".
For 1 digit: 0 = morning; 1 = afternoon.
0
Static IP(0) / Dynamic distribution IP(1)
192
IP address 192.168.1.5
168
IP address 192.168.1.5
1
IP address 192.168.1.5
5
IP address 192.168.1.5
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
0
Netmask 255.255.255.0
192
Default gateway 192.168.1.1
168
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
Explanation
8-24
Explanation
[Figure 7]