Per-unit of System Inertia
Settings
 Decrease the setting value if there is high frequency spur which occurs on Iq current
command of ASR. If the response of sudden load is too slow, then increase the setting
value.
ASR1/ASR2 Switch Frequency
Settings
 Low-speed/ high speed switch point of ASR in FOC area. This provides higher response in
high speed area and lower response in low speed area to meet customers demand. It is
suggested that the switch point should >Pr10-39.
 If the setting value is too low, it will not cover Pr10-39. If it's too high, the range of high speed
will be too narrow.
ASR1 Low-speed Bandwidth
Settings
ASR2 High-speed Bandwidth
Settings
Zero-speed Bandwidth
Settings
 After estimating inertia and set Pr.11-00 to bit 0=1 (auto tuning), user can adjust
parameters Pr.11-03, 11-04 and 11-05 separately by speed response. The larger number
you set, the faster response you will get. Pr.11-02 is the switch frequency for
low-speed/high-speed bandwidth.
 Position control pulse command (MIx=37) and P2P position control Kp gain can adjust
Pr11-05. The higher the value, the lower the steady-state error.
ASR (Auto Speed Regulation) control (P) 1
Settings
ASR (Auto Speed Regulation) control (I) 1
Settings
ASR (Auto Speed Regulation) control (P) 2
Settings
Chapter 12 Description of Parameter SettingsCT2000 Series
1~65535 (256=1PU)
5.00~599.00Hz
1~40Hz (IM)/ 1~100Hz (PM)
1~40Hz (IM)/ 1~100Hz (PM)
1~40Hz (IM)/ 1~100Hz (PM)
0~40 Hz (IM)/ 0~100Hz (PM)
0.000~10.000 sec.
0~40 Hz (IM)/ 0~100Hz (PM)
12.2-00-18
Factory Setting: 256
Factory Setting: 7.00
Factory Setting: 10
Factory Setting: 10
Factory Setting: 10
Factory Setting: 10
Factory Setting: 0.100
Factory Setting: 10