Chapter 12 Description of Parameter SettingsCT2000 Series
Inter nal
frequency
command
Zero-speed Mode
Settings
 When the frequency is less than Fmin (Pr.01-07 or Pr.01-41), it will operate by this parameter.
 When it is set to 0, the AC motor drive will be in waiting mode without voltage output from terminals
U/V/W.
 When setting 1, it will execute DC brake by Vmin(Pr.01-08 and Pr.01-42) in V/f, VFPG and SVC
modes. It executes zero-speed operation in VFPG and FOCPG mode.
 When it is set to 2, the AC motor drive will run by Fmin (Pr.01-07, Pr.01-41) and Vmin (Pr.01-08,
Pr.01-42) in V/f, VFPG, SVC and FOCPG modes.
 In V/f, VFPG and SVC modes
fout
fmin
01-07
 In FOCPG mode, when Pr.01-34 is set to 2, it will act according Pr.01-34 setting.
fout
fmin
01-07
V/f Curve Selection
Settings
01- 28
fa ll in g fr eq ue ncy
01- 29
01- 30
01- 31
01- 32
01- 33
0
F requenc y s etting command
0: Output waiting
1: Zero-speed operation
2: Fmin (Refer to Pr.01-07, 01-41)
01-34=0
stop output
0Hz
stop waiting for output
01-34=0
frequency command
0: V/f curve determined by group 01
1: 1.5 power curve
2: Square curve
r isi ng fre qu en cy
01-34=1
0Hz
0Hz oper ation
(D C br ake)
01-34=1
frequency command
12.1-01-9
Factory Setting: 0
01-34=2
01-34=2
Factory Setting: 0