Chapter 12 Description of Parameter SettingsCT2000 Series
Output frequency
(H)
Output voltage
07-09 Current Limit
for Speed Search Speed
FWD Run
B.B. Search with minimum output frequency upward timing chart
Output frequency(H)
Output voltage(V)
Output current
06-03
Over-Current Stall
Prevention
during Accel.
FWD Run
Current Limit for Speed Search
Settings
 Following a momentary power loss, the AC motor drive will start its speed search operation only if
the output current is greater than the value set by Pr.07-09.
 When executing speed search, the V/f curve is operated by g roup 1 setting. The maximum current
for the optimum accel./decel. and start speed search is set by Pr.07-09.
 The speed search level will affect the synchronous time. It will get the synchronization faster when
this parameter is set to larger value. But too large value may active overload protection.
Treatment to Reboots After Fault
Settings
 In PG control mode, the AC motor drive will execute the speed search function automatically by
the PG speed when this setting isn't set to 0.
 Fault includes: bb,oc,ov,occ etc. To restart after oc, ov, occ, Pr.07-11 can not be set to 0.
(V)
output current A
B.B.
A
B.B.
B.B. Search with minimum output frequency upward timing chart
20~200%
0: No function
1: Speed search starts with current speed
2: Speed search starts with minimum output frequency
Time
Input B.B. signal
Stop voltage output
Disable B.B. signal
Waiting time Pr.07-08
Speed search
Synchronization speed detection
Time
12.1-07-4
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection
Factory Setting: 100
Factory Setting: 0