NOTE 01: To know the current position, read 6064.
NOTE 02: To know if the position reaches the targeting position, read bit 10 of 6041. (0: reached, 1:
Not reached)
NOTE 03: To know if the position is over the limited area, read bit 11 of 6041 (0: in the limit, 1: over
the limit)
Home mode
1. Set Pr00-12 to choose a home method.
2. Set the left and right limits correspond to the position of MI terminal.
3. To switch Ac Motor Drive control mode to Home mode: Set Index 6060 = 6.
4. To switch from current mode to Operation Enable: Set 6040 = 0xE, then set 6040 = 0xF.
5. To trigger an ACK signal: Set 6040 = 0x0F, then set 6040 = 0x1F (Bit4 changes from 0 to 1 and the
motor drive will be back to home.)
Note 01: To know if the home mode is completed, read bit 12 of 6041. (0: reached, 1: Not reached)
15.3.3
By using Delta Standard (Old definition, only support speed mode)
15-3.3.1 Various mode control method (by following DS402 standard)
If you want to use DS402 standard to control the motor drive, please follow the steps below:
1.
Wiring for hardware (Refer to chapter 15.2 Wiring for CANopen)
2.
Operation source setting: set Pr.00-21 to 3 for CANopen communication card control.
3.
Frequency source setting: set Pr.00.20 to 6. (Choose source of frequency commend from
CANopen setting.)
Chapter 15 CANopen Overview CT2000 Series
15-13