Delta CT2000 Series User Manual page 60

Table of Contents

Advertisement

Model
HP
VFD110CT43A21C
15
VFD150CT43A21C
20
VFD185CT43A21C
25
VFD220CT43A21C
30
VFD300CT43A21C
40
VFD370CT43A21C
50
VFD450CT43A00C
60
VFD550CT43A00C
75
DC Reactor
DC reactor can increase the impedance, improve the power factor, decrease input current, increase
system's capacity and decrease harmonic which generates from AC motor drive. Furthermore, DC reactor
can steady the DC voltage of AC motor drive. Compare with the reactor which sets up at input side, it is
small, lower price, and low pressure drop.
Method of set up
DC reactor sets up between +1 and +2 of the circuit, and the jumper should be removed. See
the figure below:
Max.
Rated Amps
continuous
(Arms)
Amps
(Apeak)
Light
Heavy
Light
Heavy
Duty
Duty
Duty
Duty
24
17
41
36
32
23
54
49
38
30
64
64
45
36
76
76
60
43
102
91
73
57
124
121
91
69
154
146
110
86
187
182
DC reactor (optional)
Jumper
DC reactor setup
Chapter 7 Optional AccessoriesCT2000 Series
3% reactor
5% reactor
(mH)
(mH)
Light
Heavy
Light
Heavy
Duty
Duty
Duty
Duty
0.881
1.174
1.468
2.07
0.66
0.881
1.100
1.53
0.639
0.66
1.065
1.17
0.541
0.639
0.902
0.98
0.405
0.541
0.675
0.82
0.334
0.405
0.557
0.62
0.267
0.334
0.445
0.51
0.221
0.267
0.368
0.41
7-7
3%
Built-in
input reactor Delta part#
DC
reactor
Light Duty
Heavy Duty
DR024AP880
DR018A0117
X
DR032AP660 DR024AP880
X
DR038AP639 DR032AP660
X
DR045AP541 DR038AP639
X
DR060AP405 DR045AP541
X
DR073AP334 DR060AP405
X
DR091AP267 DR073AP334
X
DR110AP221 DR091AP267
X
Motor

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents