Chapter 12 Description of Parameter SettingsCT2000 Series
Feedback Signal Detection Time
Settings
 Pr.08-08 is valid only if the feedback signal is ACI.
 This parameter sets the detection time of abnormal PID derative. If detection time is set to 0.0,
detection function is disabled.
Feedback Signal Fault Treatment
Settings
 This parameter is valid only when the feedback signal is ACI.
 AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder) feedback)
are abnormal.
Sleep Frequency
Settings
Wake-up Frequency
Settings
Sleep Time
Settings
 If the command frequency falls below the sleep frequency, for the specified time in Pr. 08-12, then
the drive will shut off the output and wait until the command frequency rises above Pr.08-11.
Wake-up frequency
Sleep frequency
PID Deviation Level
Settings
PID Deviation Time
Settings
0.0~3600.0 sec
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0.00~599.00Hz
0.00~599.00Hz
0.00~6000.0 sec
Frequency command
08-11
08-10
sleep time
1.0~50.0%
0.1~300.0 sec
actual output frequency
08-12
Sleep Function
12.1-08-6
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.0
0Hz
Factory Setting: 10.0
Factory Setting: 5.0