Chapter 12 Description of Parameter SettingsCT2000 Series
Feedback Signal Detection Time
Settings
Pr.08-08 is valid only if the feedback signal is ACI.
This parameter sets the detection time of abnormal PID derative. If detection time is set to 0.0,
detection function is disabled.
Feedback Signal Fault Treatment
Settings
This parameter is valid only when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder) feedback)
are abnormal.
Sleep Frequency
Settings
Wake-up Frequency
Settings
Sleep Time
Settings
If the command frequency falls below the sleep frequency, for the specified time in Pr. 08-12, then
the drive will shut off the output and wait until the command frequency rises above Pr.08-11.
Wake-up frequency
Sleep frequency
PID Deviation Level
Settings
PID Deviation Time
Settings
0.0~3600.0 sec
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
0.00~599.00Hz
0.00~599.00Hz
0.00~6000.0 sec
Frequency command
08-11
08-10
sleep time
1.0~50.0%
0.1~300.0 sec
actual output frequency
08-12
Sleep Function
12.1-08-6
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.0
0Hz
Factory Setting: 10.0
Factory Setting: 5.0