Chapter 11 Summary of Parameter SettingsCT2000 Series
Pr.
Coefficient Gain in Actual Output
00-05
Frequency
00-06
Software Version
Parameter Protection Password
00-07
Input
Parameter Protection Password
00-08
Setting
00-09
Reserved
00-10
Control Mode
00-11
Control of Speed Mode
Explanation
Settings
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital
input (d.)
20: The corresponding CPU pin status of digital
output (0.)
21: Actual motor position (PG1 of PG card) (P.)
The max. value showed as 32bits
22: Pulse input frequency (PG2 of PG card) (S.)
23: Pulse input position (PG2 of PG card) (q.)
The max. value showed as 32bits
24: Position command tracing error (E.)
25: Overload count (0.00~100.00%) (h.)
26: Ground Fault GFF (Unit :%)(G.)
27: DC Bus voltage ripple (Unit: Vdc) (r.)
28: Display PLC data D1043 (C)
29: Display PM motor pole section (EMC-PG01U
application) (4.)
30: Display output of user defined (U)
31: Display Pr.00-05 user Gain(K)
32: Number of actual motor revolution during
operation (PG card plug in and Z phase signal
input) (Z.)
33: Motor actual position during operation (when
PG card is connected)(q)
34: Operation speed of fan(%) (F.)
35: Control Mode display: 0= Speed control mode
(SPD), 1= torque control mode (TQR) (t.)
36: Present operating carrier frequency of drive
(Hz) (J.)
37: Reserved
38: Display drive status (6.)
39: Display estimated output torque, postitive and
negative, using Nt-m as unit (t 0.0: postitive
torque; -0.0: negative torque (C.)
40: Torque command (L.) (Unit: %)
41: Display the kWH (J) (Unit: kWH)
42: PID Reference (h.) (Unit: %)
43: PID offset (o.) (Unit: %)
44: PID Output Fcmd(Hz) (b.) (Unit: Hz)
45: Hardware ID
0.00~160.00
Read-only
0~65535
0~4: the times of password attempts
0 ~ 65535
0: No password protection / password is entered
correctly (Pr00-07)
1: Parameter is locked
0: Speed mode
1: Point-to-Point position control
2: Torque mode
3: Home mode
0: VF (IM V/f control)
1: VFPG (IM V/f control+ Encoder)
2: SVC(IM Sensorless vector control)
3: FOCPG (IM FOC vector control+ encoder)
4: FOCPG(PM FOC vector control + Encoder)
11-2
Factory
Setting
1.00
#.#
0
0
0
0