Chapter 11 Summary of Parameter SettingsCT2000 Series
Pr.
01-23
1st/4th Accel/decel Frequency
01-24
S-curve Acceleration Begin Time 1
01-25
S-curve Acceleration Arrival Time 2
01-26
S-curve Deceleration Begin Time 1
01-27
S-curve Deceleration Arrival Time 2
Skip Frequency 1 (upper limit)
01-28
Skip Frequency 1 (lower limit)
01-29
Skip Frequency 2 (upper limit)
01-30
Skip Frequency 2 (lower limit)
01-31
Skip Frequency 3 (upper limit)
01-32
Skip Frequency 3 (lower limit)
01-33
01-34
Zero-speed Mode
01-35
Output Frequency of Motor 2
01-36
Output Voltage of Motor 2
01-37
Mid-point Frequency 1 of Motor 2
01-38
Mid-point Voltage 1 of Motor 2
01-39
Mid-point Frequency 2 of Motor 2
01-40
Mid-point Voltage 2 of Motor 2
01-41
Min. Output Frequency of Motor 2
01-42
Min. Output Voltage of Motor 2
01-43
V/f Curve Selection
Optimal Acceleration/Deceleration
01-44
Setting
Explanation
Settings
0.00~599.00Hz
Pr.01-45=0: 0.00~25.00 second
Pr.01-45=1: 0.0~250.0 second
Pr.01-45=0: 0.00~25.00 second
Pr.01-45=1: 0.0~250.0 second
Pr.01-45=0: 0.00~25.00 second
Pr.01-45=1: 0.0~250.0 second
Pr.01-45=0: 0.00~25.00 second
Pr.01-45=1: 0.0~250.0 second
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0.00~599.00Hz
0: Output waiting
1: Zero-speed operation
2: Fmin (Refer to Pr.01-07, 01-41)
0.00~599.00Hz
460V: 0.0V~510.0V
0.00~599.00Hz
460V: 0.0V~480.0V
0.00~599.00Hz
460V: 0.0V~480.0V
0.00~599.00Hz
460V: 0.0V~480.0V
0: V/f curve determined by Pr.01-00~01-08
1: Curve to the power of 1.5
2: Curve to the power of 2
3: 60Hz, voltage is saturated when it's 50Hz
4: 72Hz, voltage is saturated when it's 60Hz
5: 50Hz, decrease gradually with third power
6: 50Hz, decrease gradually with square
7: 60Hz, decrease gradually with third power
8: 60Hz, decrease gradually with square
9: 50Hz, medium starting torque
10: 50Hz, large staring torque
11: 60Hz, medium starting torque
12: 60Hz, large starting torque
13: 90Hz, voltage is saturated when it's 60Hz
14: 120Hz, voltage is saturated when it's 60Hz
15: 180Hz, voltage is saturated when it's 60Hz
0: Linear accel. /decel.
1: Auto accel.; linear decel.
2: Linear accel.; auto decel.
3: Auto accel./decel.
4: Linear, stall prevention by auto accel./decel. (limit
by Pr.01-12~01-21)
11-8
Factory
Setting
0.00
0.20
0.2
0.20
0.2
0.20
0.2
0.20
0.2
0.00
0.00
0.00
0.00
0.00
0.00
0
60.00/
50.00
400.0
3.00
22.0
1.50
10.0
0.50
2.0
0
0