Reserved
Communication Decoding Method
Settings
Source of
Digital Keypd
Operation
External
Control
Terminal
RS-485
CANopen
Communication
Card
PLC
Internal Communication Protocol
Settings
Reserved
PLC command force to 0
Settings
Chapter 12 Description of Parameter SettingsCT2000 Series
0: Decoding Method 1 (20xx)
1: Decoding Method 2 (60xx)
Decoding Method 1
Digital keypad controls the drive action regardless decoding method 1 or 2.
External terminal controls the drive action regardless decoding method 1 or 2.
Refer to address: 2000h~20FFh
Refer to index: 2020-01h~2020-FFh
Refer to address: 2000h ~ 20FFh
PLC commands the drive action regardless decoding method 1 or 2.
0: Modbus 485
-1: Internal Communication Slave 1
-2: Internal Communication Slave 2
-3: Internal Communication Slave 3
-4: Internal Communication Slave 4
-5: Internal Communication Slave 5
-6: Internal Communication Slave 6
-7: Internal Communication Slave 7
-8: Internal Communication Slave 8
-9: Reserve
-10: Internal Communication Master
-11: Reserve
-12: Internal PLC Control
0~65535
12.1-09-12
Factory Setting: 1
Decoding Method 2
Refer to address: 6000h ~ 60FFh
Refer to index:2060-01h ~ 2060-FFh
Refer to address: 6000h ~ 60FFh
Factory Setting: 0
Factory Setting: 0